此页面上的内容需要较新版本的 Adobe Flash Player。

获取 Adobe Flash Player

KGN-12kV armored fixed type miniaturized switchgear

Update: 2016/9/2      View:
  • Brand:    
  • Type:    
  • Order Online
Introduction

Product introduction

1 product introduction:

Dworp electrical R & D and production of kgn] - 12 new armor fixed switching equipment, the products with domestic advanced technology, can be in comprehensive performance and technical indicators are better than the market existing fixed cabinet. Widely used in power plants, medium and small generators power transmission, industrial and mining enterprises and distribution and other occasions, out of control, protection, monitoring.

The product meets the requirements of the GB3906-2006 standard for high voltage switchgear, the main switch used for the miniaturization of the VH9-12 vacuum circuit breaker products to meet the "five defense" and the protection level requirements.

2 model meaning:

3 use conditions:

Normal use of environmental conditions:

A, ambient temperature: upper limit of +40;

B, not more than 1000 meters above sea level;

C, air relative humidity: daily average of not more than 95%, the monthly average of not more than 90%;

D, the seismic intensity is not more than 8 degrees;

E, does not apply to corrosive or flammable gases, water vapor and other places of obvious pollution.

Note: beyond the normal use conditions, the user can consult with the manufacturer to determine.

1 product features:

1, product structure features overview

1.1 a switch cabinet body using aluminized zinc plate, the CNC machining and take multi folding technology, make the whole cabinet body not only has the advantages of high precision, strong corrosion resistance and antioxidation and due to the adoption of the multi folding technology, the cabinet has light overall weight, compared with other similar equipment cabinets, high mechanical strength, beautiful appearance. Cabinet with assembled structure, covers an area of small, easy to organize production.

1.2 small size cabinet, saving the occupied area and space.

1.3 main switch for miniaturized vacuum circuit breaker and modular design structure makes the replacement body parts is simple and convenient. Arc extinguishing device adopts horizontal installation and vacuum arc extinguishing chamber adopts domestic advanced manufacturers of products, ensure product excellent breaking, closing and dynamic thermal stability. And the circuit breaker with a fixed installation, greatly improving the circuit breaker dynamic thermal stability and makes operation more simple, circuit breaker voltage, parameter measurement, and other more convenient.

1.4 isolating switch for the design of miniaturized isolating switch and the isolating switch is the rotation of the screw driven dynamic contact horizontal trolley forward and back off of, contact connection mode is static end by selecting a small volume, high reliability of the watch chain structure. Grounding switch is dividing and combining with worm drive. Operation, labor saving, reliable, miniaturization design effectively reduced the size of the switch cabinet.

1.5 has a reliable "five anti" function. The front door has forced mechanical locking, the operation mode is rotary type, convenient, flexible, and labor saving.

2, the circuit breaker room is located in the middle of the front part of the cabinet body is, using a circuit breaker has the advantages of novel structure, excellent performance of vacuum circuit breaker. Circuit breaker chamber is provided with a pressure releasing chamber, to release internal fault electric arc generated by the pressure to ensure switch cabinet and the safety of the operator; cabinet door is provided with an inspection window, observable isolation switch position.

3, bus room is located in the middle to upper part of the cabinet body, main bus through the branch bus bar and the isolating switch is connected, in the bus through the switch cabinet by wall bushing is fixed, the accident, limiting the spread to the adjoining cabinets, and to ensure that the mechanical strength of the bus.

4, relay instrument indoor installation of relay protection and measurement instruments, switching switch, live display device, signal lights and other control, protection, signal equipment.

1 implementation standards:

GB3906-91<3 ~ 35kV AC metal enclosed switchgear

General specification for GB11022-89< High Voltage Switchgear Equipment >